Cordex® CXC HP HV-ADIO

The Cordex® CXC HP HV-ADIO brings advanced control and monitoring to Alpha® Cordex® 125/220Vdc rectifiers and systems.

Request a Quote
select a product's specifications tab

The HV-ADIO is part of the CXC HP series of advanced I/O peripheral incorporating flexible mounting, high accuracy, and the advanced features in the HP control platform. The HV-ADIO provides a variety of analog inputs, digital inputs and high voltage rated relay outputs. The ADIO device is seamlessly recognized by the CXC HP control platform which also provides advanced setup wizards to create high voltage DC systems using Cordex rectifiers.

An integrated Ground Fault Detection (GFD) circuit is also provided to enable visibility to earth leakage currents. This feature can be easily disabled for operators who wish to use 3rd party GFD devices. Cordex® CXC HP controllers and ADIO peripherals ensure effortless operation and management capability to satisfy the most demanding and advanced energy system applications.

Request a Quote
  • CXC HP series ADIO peripheral with flexible rack, panel, and DIN mounting options
  • Enables High Voltage (125/220Vdc) system support using the advanced CXC HP Control platform
  • I/O expansion via CAN bus for advanced site monitoring applications, including support for future growth
  • Integrated Ground Fault Detection (GFD) to alarm system fault conditions
  • On board DC-DC converter permits use with standard CXC HP low voltage controllers

Product Specification

Take a look at the following Cordex® CXC HP HV-ADIO product specification:

Product Type

Peripherals

Application

Small Cells

Macro Cells

In-building Wireless

Passive Optical LANs

Inside Plant

5G, Small Cells & WiFi

Public Safety Networks

Security & Surveillance

Traffic & Intelligent Transportation Systems (ITS)

Edge Computing

Mobile Core

Outdoor Small Cells

Private 5G Networks

5G Macro Cells

Input Power

50W (125Vdc 0.4A; 220Vdc 0.2A)

Input Voltage

90 to 300Vdc

Local Alarms

Power ON (Blue) / Communications OK (Green)

Communications Ports

CAN In/Out (RJ12 Offset)

Voltage Inputs

2 (±300Vdc

Current Shunt Inputs

1 (25 to 200mV)

Temperature Inputs

2

Digital Inputs

4 (Contact closure detect – 5Vdc Max)

Relay Outputs

6 (Form C, 220Vdc 50W max

Mounting

CXC HP 3U rack panel mount (0180046) or DIN/Panel mounting

Dimensions H x W x D (inches)

7.8 x 3.3 x 1.5

Dimensions H x W x D (mm)

198 x 84 x 38